An autotransformer starter reduces motor terminal voltage during acceleration. The network sees less starting current, but the load also receives less motor torque.

Calculate the tap effect

As a screening relationship:

Starting torque at tap β‰ˆ full-voltage starting torque Γ— tap voltageΒ²

A 0.8 per-unit voltage tap therefore produces roughly 0.8Β² = 0.64 per-unit of the full-voltage starting torque. Final approval must use the actual motor curve and starter connection.

Check Required input Pass condition
Bus voltage Source impedance and other loads Above project minimum
Acceleration Motor/load torque-speed curves and inertia Positive margin through run-up
Thermal duty Acceleration time and starts/hour Within motor and starter limits
Transition Circuit sequence and timing Acceptable current/torque disturbance

Model the worst credible supply and loaded-start condition. Protection settings must allow legitimate acceleration without leaving a stalled motor energized beyond its withstand time.

Commission by trending bus voltage, motor current and acceleration time. Compare results with the study and investigate a slower-than-predicted start before increasing trip settings.