A short interruption can stop a contactor while the process and rotor continue moving. Reclosing without a sequence review can produce mechanical shock, high current or an unsafe unattended start.

Dip outcome Required decision Evidence
Contactor holds Ride-through remains acceptable Coil and control-voltage test
Contactor drops Restart allowed or inhibited Cause-and-effect logic
Motor coasts Residual speed/direction known Coast-down data
Multiple motors return Staggered priority required Bus reacceleration study

Define restart permission

Classify each motor by process consequence. Pumps may need valve state and minimum-flow checks; conveyors may contain material; compressors may need unloading and pressure equalisation. A VFD flying start must be commissioned for both speed and direction ranges actually permitted.

Retain event duration, minimum voltage, contactor states, speed, current and process permissives from witnessed tests. Do not increase protection delays merely to force a restart through an unexplained condition.

Related reading: VFD flying start and motor starting voltage drop.