Common-mode chokes address current shared by conductors relative to earth. They do not correct every differential-mode harmonic or replace bonding, shield termination and a low-inductance return path.

Map common-mode current before adding impedance

First verify 360-degree motor-cable shield termination, enclosure bonding and PE continuity. Then use measurements to distinguish bearing current, encoder disturbance and conducted emissions. A choke chosen without this diagnosis may shift the resonance.

Current-path review

Item Engineering purpose Review action
Source Drive switching edges Identify voltage and carrier settings
Path Cable, frame and bearings Measure where current closes
Choke Common-mode impedance Check saturation and heating
Bonding Shield and PE connections Reduce uncontrolled return paths

Evidence required before approval

Document core material, turns, conductor arrangement, current rating and temperature rise. Repeat measurements after installation and retain before-and-after spectra under comparable load.

Retain the equipment revision and test record. Name the reviewer. Keep open assumptions visible.

Commissioning decision

Never approve a copied setting. Confirm interface compatibility and operating limits. Exercise the intended response during a functional test.